- SECTION 08465
-
- AUTOMATIC FOLDING DOORS
- NOTE ** Dor-O-Matic automatic folding door packages,
- including operators, actuators, safeties and
- hardware.
- NOTE **
- NOTE ** This section is based on the products of Dor-O-
- Matic, which is located at:
- NOTE ** 7530 W. Wilson Avenue
- NOTE ** Harwood Heights, IL 60656-4786
- NOTE ** Tel: (708) 867-7400
- NOTE ** Tel: (800) 543-4635
- NOTE ** Fax: (708) 867-0291
-
- NOTE ** Dor-O-Matic is one of the oldest, most experienced,
- and most innovative manufacturers of automatic door
- equipment in the world. This section covers only a
- part of their product line: "Astro-Fold" folding
- doors, panels, jambs, and operators, with
- accompanying control components, including motion
- detectors and advanced infrared safety systems.
- See their other sections for automatic swinging
- doors, automatic sliding doors, fire door
- operators, and ADA-compliant low-energy operators.
- NOTE **
- NOTE ** SECTION 08465 - AUTOMATIC FOLDING DOORS, Copyright
- 1998, The Architect's Catalog, Inc.
-
- PART 1 GENERAL
-
- 1.1 SECTION INCLUDES
-
- A. Aluminum folding doors and frames.
-
- B. Automatic door operators, actuators, and safeties.
- NOTE ** Delete the following if not required for project.
-
- C. Fail-safe magnetic locking package.
-
- 1.2 RELATED SECTIONS
- NOTE ** Delete any sections below not relevant to this
- project; add other as required.
-
- A. Section 03300 - Cast-in-Place Concrete: Recess in
- concrete slab for mat-type actuators.
-
- B. Section 07900 - Joint Sealers.
-
- C. Section 08800 - Glass and Glazing.
-
- D. Division 16 - Electrical: 115 VAC, single-phase wiring
- in conduit between operator enclosure and building power
- supply and low voltage wiring between enclosure and
- actuators and safeties.
-
- 1.3 REFERENCES
-
- A. ANSI/BHMA A156.10 - American National Standard for Power-
- Operated Pedestrian Doors.
-
- B. NFPA 101 - Safety to Life from Fire in Buildings and
- Structures.
-
- C. UL 325 - Standard for Door, Drapery, Gate, Louver, and
- Window Operators and Systems.
-
- 1.4 DEFINITIONS
-
- A. FS Panel: The panel (half of a pair of bifolding doors)
- which hinges to the door jamb.
-
- B. FX Panel: The panel (half of a pair of bifolding doors)
- which locks to the door jamb in a bi-folding single
- application, or meets another panel in a bi-folding pair
- application.
-
- 1.5 PERFORMANCE REQUIREMENTS
-
- A. Automatic opening and closing of folding doors by way of
- inside and outside motion detectors and electro-
- mechanical operators; adjustable opening speed, closing
- speed, and hold open duration.
-
- B. Maximum security lock cylinders, keyed alike; one
- interior thumbturn.
-
- C. Emergency one-point unlocking system; releasing interior
- thumbturn in one operation allows doors to swing in the
- direction of egress.
-
- D. Adjustable ball/detent system allows folding door to
- swing out 90 degrees for manual breakout from any
- position in cycle, complying with NFPA 101.
-
- E. Power to door operator disconnected when folding doors
- are in emergency swing out position.
- NOTE ** Delete the following if fail-safe magnetic locking
- package is not required for the project.
-
- F. Fail-safe magnetic locks prevent doors from opening
- except that, upon power failure, doors unlock allowing
- exit by use of the breakaway system.
-
- 1.6 SUBMITTALS
-
- A. Submit under provisions of Section 01300.
-
- B. Product Data: Manufacturer's catalog data, detail
- sheets, and specifications.
-
- C. Shop Drawings: Prepared specifically for this project;
- show dimensions of doors, operators, and interface with
- other products.
-
- D. Operating and Maintenance Data: Operating and
- maintenance instructions, parts lists, and wiring
- diagrams.
-
- 1.7 QUALITY ASSURANCE
-
- A. Installer Qualifications: Factory-trained, with minimum
- 3 years experience.
-
-
- PART 2 PRODUCTS
-
- 2.1 MANUFACTURERS
-
- A. Acceptable Manufacturer: Provide products made by Dor-O-
- Matic, 7350 West Wilson Avenue, Harwood Heights, IL 60656-
- 4786. ASD. Tel: (708) 867-7400 or (800) 543-4635. Fax:
- (708) 867-0291.
-
- B. Requests for substitutions will be considered in
- accordance with provisions of Section 01600.
- NOTE ** Delete paragraph above or below; coordinate with
- Division 1 requirements.
-
- C. Substitutions: Not permitted.
-
- D. Provide all automatic folding doors, panels, jambs, and
- electro-mechanical automatic door operating equipment
- from a single manufacturer.
-
- 2.2 DOORS AND FRAMES
- NOTE ** Automatic folding doors are available from Dor-O-
- Matic in complete packages including aluminum
- doors, panels, jambs, operators, and actuators.
-
- A. Doors, Panels, and Jambs: Extruded aluminum alloy,
- minimum 1/8 inch (3.17 mm) thick.
- 1. Door and Panel Construction: Heavy-duty interlocked
- sections, through-rod bolted.
- 2. Top Web of Doors: 1/4 inch (6.34 mm) thick, factory-
- prepared with custom steel press nuts to accept
- required hardware.
- NOTE ** For aluminum doors, natural anodized and dark
- bronze anodized are the two standard finishes; many
- other finishes, including black anodized, Kynar,
- and metal clad, are available. Select one of the
- following three paragraphs.
- 3. Finish: Natural anodized aluminum.
- 4. Finish: Dark bronze anodized aluminum.
- 5. Finish: __________.
- NOTE ** Following is an example of specifying operator and
- actuators when more than one configuration is used
- on the project and the drawings do not call out
- such details.
- 6. Motor/Gear Box Operator: Full size, heavy-duty self-
- contained electro-mechanical, concealed overhead.
- NOTE ** Usually, delete all but one of the following six
- paragraphs. Under some conditions, more than one
- actuator is appropriate for a single door opening.
- 7. Actuator: Motion detector.
- 8. Actuator: Push plate.
- 9. Actuator: Key switch.
- 10. Actuator: Card reader.
- 11. Actuator: Mat type.
- 12. Actuator: ________.
- NOTE ** Include the following safety devices for all
- automatic folding doors.
- 13. Safety System: One overhead-mounted infrared safety
- sensor, two horizontal safety beams, and two
- microwave motion detectors; mount one motion detector
- on each side of door opening.
- 14. Finger Guards: 1 inch (25 mm) vinyl on doors,
- panels, and jambs.
-
- 2.3 DOOR OPERATORS
-
- A. Operation: Electric power opening, closing, and holding;
- comply with ANSI A156.10 and UL 325.
- 1. Open unlocked doors upon activation of motion
- detector.
- 2. Close doors after each cycle, and hold against drafts
- and wind pressure.
- 3. Provide safety reverse function to automatically
- reverse doors to full open position should a person
- or object be encountered during closing cycle.
- 4. Spring-close closing force: 9 lb-force (40 N).
- 5. Manual switch between spring-close-and-hold and power-
- boost-close-and-hold.
- 6. Power-boost-close-and-hold: Electronically increase
- door closing force to 18 lb-force (80 N).
- 7. Provide adjustment by microprocessor control for:
- a. Opening speed.
- b. Hold open speed, from 1 to 30 seconds.
- c. Closing speed.
- 8. Factory-set door hold-open voltage.
- 9. Manual "On-Off-Hold Open" switch.
- 10. Fail safe: In event of power failure, make door
- operate manually without damage to operator
- components.
-
- B. Construction: Heavy-duty self-contained electro-
- mechanical; comply with ANSI A156.10 and UL 325.
- 1. Motor/gear box operator: Cast aluminum housing, with
- precision-machined gears and bearing seats and all-
- weather lubricant, mounted on vibration isolators.
- 2. Gears: Manufactured by door operator manufacturer
- specifically for operators.
- 3. Motor: DC permanent magnet motor with shielded ball
- bearings. Stop motor when door stops or is fully
- open and when break-away is operated.
- 4. Door operating arm: Forged steel, attached at
- natural pivot point of door; do not use slide block
- in top of door.
- 5. Microprocessor control: 115 VAC. Do not use rotary
- arm mechanism or door position switches along header.
- Mount control in snap-in type control box.
- 6. "On-Off-Hold Open" switch: Three-position toggle or
- rocker type.
- 7. Control circuits for actuators and safeties: Low
- voltage, NEC Class II.
- 8. Service conditions: Satisfactory operation between
- minus 30 degrees F (minus 34 degrees C) and 160
- degrees F (71 degrees C).
- 9. Power supply required: 115 VAC.
-
- C. Enclosure: Overhead header, 9 inches high by 6 inches
- wide (230 x 152 mm), containing all operating components.
- 1. Provide access door on bottom of enclosure for access
- to controls and removable components without removal
- of door or operator.
- 2. No exposed fasteners.
- NOTE ** Delete three of the following four paragraphs.
- Anodized aluminum is the standard finish for
- exposed headers. Clad finish applies to storefront
- or curtainwall installations where the adjacent
- finish is bronze or stainless, or other metal
- finish. If coated finishes are specified, the
- color should be specified, especially if it must
- match the doors.
- 3. Finish of Exposed Surfaces: Match doors.
- 4. Finish of Exposed Surfaces: Anodized aluminum.
- 5. Finish of Exposed Surfaces: Factory coated, Kynar
- 500(tm).
- 6. Finish of Exposed Surfaces: Clad to match door
- frame.
- NOTE ** Usually, delete all but one of the following six
- paragraphs. If clad metal finish is specified,
- delete all six paragraphs.
- 7. Color: To match door.
- 8. Color: As selected from manufacturer's standard
- selection.
- 9. Color: Dark bronze.
- 10. Color: Natural aluminum.
- 11. Color: Black.
- 12. Color: ________.
-
- 2.4 ACTUATORS
- NOTE ** Select actuators from below; delete those not
- required for the project. Actuators can be motion
- detectors on both sides of header, push plates,
- card readers, or other momentary contact devices.
-
- A. Motion Detectors: Dor-O-Matic "Astro-Scan".
- NOTE ** Delete one of the following two paragraphs. The
- first is the standard motion detector. The second
- is a one-way detector that can distinguish between
- approaching and departing traffic - this is mostly
- used for two-way traffic through the same door (a
- motion detector on each side).
- 1. Operation: Detect movement within adjustable zone
- near door and activate operator; deactivate operator
- upon no movement.
- 2. Operation: Detect approaching movement within
- adjustable zone near door and activate operator;
- deactivate operator upon no movement or departing
- movement.
- 3. Adjustable sensitivity and time delay.
- 4. Housing: Black anodized aluminum.
- 5. Lens: Black Lexan, screwed on; sealed to provide
- weather- and dust-proofing.
- 6. Mounting: Flush against header/wall.
- 7. Operating unit: Gimbal-mounted oscillator allowing
- pattern adjustment.
- 8. Electronics: Removable printed circuit board with
- gold-plated contacts; unaffected by radio frequency
- interference, normal police, fire, and ambulance
- frequencies, and other two-way radio frequencies;
- designed to eliminate line noise and surge current.
- 9. Service conditions: Satisfactory operation between
- minus 30 degrees F (minus 34 degrees C) and 160
- degrees F (71 degrees C); unaffected by humidity or
- moisture.
-
- B. Push Plate Actuator: Formed metal plate with rounded
- corners, satin finish; approximately 5 inches (127 mm)
- square; with depressed marking.
- NOTE ** Delete one of the following two paragraphs.
- 1. Material: Stainless steel.
- 2. Material: Brass.
- NOTE ** Delete one of the following two paragraphs.
- 3. Marking: "Push to operate door", filled red.
- 4. Marking: Handicapped symbol, filled blue.
-
- C. Card Reader Actuator: _____________.
-
- D. Key Switch Actuator: ____________.
-
- E. Mat-Type Actuator/Safety: Manufacturer's standard rubber
- mat type.
- 1. Frame for recessed mounting in floor slab.
- 2. Frame for surface mounting, with transition strips.
- 3. Color: As selected from manufacturer's standard
- selection.
- 4. Color: _________.
-
- 2.5 HARDWARE AND ACCESSORIES
-
- A. Door Hardware:
- 1. Manual Locks: Emergency one-point unlocking system,
- Adams-Rite maximum security lock cylinders, keyed
- alike.
- NOTE ** Select the first subparagraph below for bi-folding
- single doors, the second subparagraph for bi-
- folding pairs.
- a. Quantity: Two per opening.
- b. Quantity: Three per opening.
- 2. Main Cylinders: One per opening, keyed on outside,
- thumbturn on inside, locking the FX panel into
- adjacent jamb and dropping vertical bolt into
- threshold/floor. Releasing interior thumbturn shall
- allow doors to swing in the direction of egress.
- 3. Secondary Cylinders: Keyed both sides, operating
- vertical bolt to lock the FS panel into breakaway
- carrier.
- 4. Pivot Systems: Extra-heavy duty, providing concealed
- radial thrust bearings at tops of panels.
- NOTE ** Include the following paragraph if threshold is
- shown on drawings or called for in schedule.
- 5. Threshold: Manufacturer's standard.
- NOTE ** Include one of the following two paragraphs if fail-
- safe magnetic locking package is required for
- project.
- 6. Fail-Safe Magnetic Locking Package (with Four-
- Position Switch):
- a. Magnetic lock control board; 12-volt DC, 2,700
- pound (12,000 N) holding force shear magnetic
- locks.
- b. Doors unlock with power failure, allowing exit by
- use of the breakaway system.
- c. Switch Position "Off": Magnetic locks and all
- sensing devices deactivated; doors still manually
- lockable.
- d. Switch Position "One-Way": Doors locked for
- night (security) operation; outside sensing
- devices deactivated, magnetic locks prevent
- forcible opening from outside; inside sensing
- devices unlock and open doors, activating outside
- sensing devices until doors are fully closed.
- e. Switch Position "Two-Way": Doors unlocked for
- day (normal) operation; inside and outside
- sensors active.
- f. Switch Position "Hold Open": Doors unlocked and
- held in full open position.
- 7. Fail-Safe Magnetic Locking Package (Wired into
- Security System):
- a. Magnetic lock control board; 12-volt DC, 2,700
- pound (12,000 N) holding force shear magnetic
- locks.
- b. Doors unlock with power failure, allowing exit by
- use of the breakaway system.
- c. Contacts Open (One-Way): Doors locked for night
- (security) operation; outside sensing devices
- deactivated, magnetic locks prevent forcible
- opening from outside; inside sensing devices
- unlock and open doors, activating outside sensing
- devices until doors are fully closed.
- d. Contacts Closed (Two-Way): Doors unlocked for
- day (normal) operation; inside and outside
- sensors active.
- NOTE ** Include the following paragraphs if magnetic lock
- override switch is required for project.
- 8. Two-Position Magnetic Lock Override Switch:
- a. Position "Off": Prevents magnetic lock from
- engaging (locking) no matter which of the four
- positions is selected; door functions as if there
- were no magnetic lock, but doors still manually
- lockable.
- b. Position "On": Magnetic lock functions as
- specified.
-
- B. Signs: Provide signs complying with ANSI A156.10 and
- applicable codes.
- 1. Approach side: Black arrow on white background
- inside green circle.
- 2. Reverse side: "DO NOT ENTER" in white letters on a
- red circle.
- 3. Traffic in both directions through same door: Yellow
- circle with "AUTOMATIC DOOR" in black letters and
- "CAUTION" across the middle in yellow letters on
- black.
-
-
- PART 3 EXECUTION
-
- 3.1 EXAMINATION
-
- A. Verify that door openings are plumb, square, and ready
- for installation of automatic folding door equipment.
-
- B. Verify that electrical service is available, properly
- located, and of proper type.
-
- 3.2 INSTALLATION
-
- A. Install folding doors, frames, operating equipment,
- hardware, and accessories in accordance with
- manufacturer's instructions; comply with ANSI A156.10.
- NOTE ** Delete the following paragraph if mat-type
- actuators are not used in project.
-
- B. Install mat-type actuators in recesses in floor; level
- and grout securely.
-
- C. Verify that electrical connections are made correctly.
-
- 3.3 ADJUST AND CLEAN
-
- A. Adjust doors and operators for proper operation, without
- binding or scraping and without excessive noise.
-
-
- END OF SECTION
-